Product Show

Location:Home >> Products >> Switching Power Supply Series

SCN-1000

Switching Power Supply Series
Keywords:
1000w swtch power supplies
Product Details

Model
Performance
SCN-1000-12
SCN-1000-13.5
SCN-1000-15
SCN-1000-24
SCN-1000-27
SCN-1000-48
DC output voltage
12V
13.5V
15V
24V
27V
48V
Output voltage tolerance(Note 2)
±1%
±1%
±1%
±1%
±1%
±1%
Rated output current
80A
71A
64A
40A
35.5A
20A
Output current range
0-40A
0-36A
0-32A
0-20A
0-18A
0-10A
Ripple and noise(Note 3)
240mVp-p
240mVp-p
240mVp-p
240mVp-p
200mVp-p
300mVp-p
Inlet stability(Note 4)
±0.5%
±0.5%
±0.5%
±0.5%
±0.5%
±0.5%
Load stability(Note 5)
±0.5%
±0.5%
±0.5%
±0.5%
±0.5%
±0.5%
DC output power
1000W
1000W
1000W
1000W
1000W
1000W
Efficiency
84%
84%
83%
85.5%
86.5%
87%
DC voltage adjustable range
10-13.2V
12-15V
13.5-18V
20-26.4V
24-30V
41-56V
Input voltage range
190~240VAC/47~63Hz;
Input current
7A/230V
Surge Current
50A/230VAC
Leakage Current
<3.5mA/240VAC
Overload protection
105%~135% type:FOLDBACK cut off output reset:Automatic recovery
over-voltage protection
13.8~16.2V
15.5~18.2V
18~21V
27.6~32.4V
31~36.5V
57.6~67.2V
High temperature protection
RTH1 OR RTH2>=55℃ FAN ON,<=45℃ FAN OFF,>=70℃ cut off output 
temperature coefficient
±0.03%℃(0~50℃)
Start-up,rise,hold up time
1.5s,50ms,20ms
shock resistance
10~500Hz,2G 10min./1circle,Period for 60min.,Each axes
Withstand voltage
Input and Output internal:3KvAC,input and enclosure:1.5KvAC,output 
and enclosure:0.5KvAC
Insulation Resistance
Input and Output internal: input and enclosure,output and enclosure:
500VDC/100M Ohms
work Temperature/humidity 
-10℃~+50℃(Refer to output derating curve),20%~90%RH
storage temperature /humidity
-20℃~+85℃,10%~95%RH
Outline dimension
291*132*68mm 
Weight
2.35Kgs
Safety standards
UL1950,TUV EN60950
EMC Standards 
CISPR22(EN55022),IEC1000-42,3,4,5,6,8,11 IEC100-3-2
Note: 
1.The above parameters test conditions: 230VAC input, rated load, 25 ℃ 70% RH Humidity.
2.Tolerance: includes set up tolerance, line stability and load stability (Note 5).
3.The ripple test: 20MHz with A12 "twisted pair, interrupted with a 0.1uF & 47uFcapacitor circuit. 
4.The incoming line voltage stability test: the minimum full load voltage of the incoming line to the highest voltage. 
5.Load stability test: the load from 0% to 100%.other output is 60% rated load.
6.The each output can reach maximum current,but the total load can't over the maximum output power.

 

Drawing: